Leadtime 6-10 weeks
Diagnostic Insulation Resistance Tester
Li-ion battery
Large LCD display with backlight
AC Voltage : 90-264 V rms, 47- 63 Hz 200 VA
Battery charge time : 2.5 hours deep discharge, 2 hours normal discharge
Test Voltage : 1000 V, 2500 V, 5000 V, 10000 V, 15000 V, User defined test voltage.
User defined test voltage : 50 V to 1 kV in 10 V steps, 1 kV to 5 kV in 25 V steps, 5 kV to 15 kV in 25 V steps
Test voltage accuracy : +4%, -0%, ±10 V nominal test voltage at 1 GΩ load (0°C to 30°C
Resistance range : 10 kΩ to 15 TΩ @ 5 kV, 10 kΩ to 20 TΩ @ 10 kV, 10 kΩ to 30 TΩ @ 15 kV
Short circuit / charge current : 3 mA @ 5 kV, 10 kV, 15 kV
Insulation test alarm: 100 kΩ to 10 GΩ
Capacitor charge : <7.5 s/μF at 3 mA to 15 kV
Capacitor discharge : <3500 ms/μF to discharge from 15 kV to 50 V
Capacitor range : 10 nF to 50 μF
Capacitance measurement accuracy : ±10% ±5 nF
Current range : 0.01 nA to 6 mA
Current accuracy : ±5% ±0.2 nA at all voltages (20 °C)
Fitur
Measures capacitance of test object (with test voltages over 5000 V)
IR, Timed IR, DAR, PI, DD, SV and Ramp diagnostic tests
High current – 3 mA short circuit current
Dedicated voltmeter function (30 V to 660 V)
Advanced memory, on screen recall and real time clock for date / time stamped results
Download of on-board results via USB interface
Recorded temperature (measured by independent instruments) can be saved with test result
PowerDB Lite asset management software
Safety rated at CAT IV 600 V (maintained to 3000 m altitude)